Skip to content

Buying LT power cables: XLPE or PVC, armour, cable codes, the ISI rule, GST and quotes

How to buy armoured and unarmoured LT power cables: IS 7098 and IS 1554, what codes like A2XFY mean, drum markings, the ISI rule, 18% GST, comparing quotes and red flags.

By The Indibaba team

7 min read

Spools of industrial cable
Stock photo. Photo credits
In this article

Low-voltage (LT) power cables up to 1100 V are made to IS 7098 (Part 1) when the insulation is XLPE (cross-linked polyethylene) and to IS 1554 (Part 1) when it is PVC. Both are under the Cables (Quality Control) Order, 2020, so they must carry the ISI mark. GST on insulated cable is 18% (Notification 9/2025-Central Tax (Rate) (opens in a new tab)). Your electrical consultant sizes the cable; your requirement should then name the standard, conductor, number of cores, size, armour and drum lengths, so that every quote is for the same cable.

Key facts

  • PVC insulated heavy-duty cables (IS 1554 Parts 1 and 2), XLPE insulated cables (IS 7098 Parts 1 to 3), aerial bunched cables (IS 14255) and elastomer insulated cables (IS 9968 Part 2) are listed under the Cables (Quality Control) Order, 2020 (BIS Scheme-I list (opens in a new tab)).
  • A BIS licence for IS 7098 (Part 1) states whether the cable is armoured or unarmoured, aluminium or copper, solid (class 1) or stranded (class 2), and the largest number of cores and size it covers (BIS product manual for IS 7098 Part 1 (opens in a new tab)).
  • Conductors are plain copper or aluminium wires complying with IS 8130 (IS 7098 (Part 1):1988, clause 3.1 (opens in a new tab)).
  • The maker must run a conductor resistance test and a high voltage test on every finished cable length as routine tests (IS 7098 Part 1, clause 15.3).

Reading a cable code

Both standards use letters to describe the cable (IS 7098 (Part 1):1988, clause 17.3 (opens in a new tab); IS 1554 (Part 1):1988, clause 17.3 (opens in a new tab)):

LetterMeaning
AAluminium conductor (no letter means copper)
2XXLPE insulation
YPVC insulation (IS 1554) or PVC outer sheath
WSteel round wire armour
FSteel strip armour
WW, FFDouble round wire or double strip armour

So "A2XFY" is an aluminium conductor, XLPE insulated, steel strip armoured cable with a PVC outer sheath, and "2XWY" is the copper version with round wire armour. Write the full code, the number of cores and the size, for example "3.5 core 240 mm² A2XFY", in your requirement.

What to put in your requirement

  • Standard and voltage: IS 7098 (Part 1) or IS 1554 (Part 1), 1100 V.
  • Conductor: aluminium or copper, size in mm² and number of cores.
  • Armour: unarmoured, strip or round wire, as the consultant specifies for the route.
  • Sheath type: ordinary, or a fire-performance type such as FR or FR-LSH if specified; IS 7098 (Part 1) as amended requires such special cables to carry the legend along the sheath.
  • Length: total metres, the drum lengths you can use, and any cut lengths.
  • Tests and documents: routine test report for each drum, and type test reports if the consultant asks for them.

Markings to check on delivery

IS 7098 (Part 1) asks for the maker's name or trade mark along the length of the cable, on a tape or indented, printed or embossed on the outer sheath, and for the word "electric" along the sheath (clause 17). Each drum must show the standard, the maker, cable type and voltage grade, number of cores, conductor size, cable code, length on the drum, gross mass, country and year of manufacture (clause 18.2). Check these against your order, and check the ISI mark and licence number.

How to compare quotes on landed cost

  1. Same cable. Same code, cores, size, conductor and armour. A copper and an aluminium cable of the same size are different products.
  2. Price basis. Per metre for the stated drum length. If a quote is per drum, divide by the drum length.
  3. Drum lengths and cut pieces. Whether you must take full drums, and what cut lengths and returnable drums cost.
  4. Tests. Whether routine test reports, and any witnessed test you ask for, are included.
  5. Freight, unloading and GST. Cable drums are heavy; ask for delivered rates to your site and GST at 18%.

GST rate and HSN code

Insulated wire and cable falls under HSN 8544. Notification 9/2025-Central Tax (Rate) lists insulated (including enamelled or anodised) wire, cable and other insulated electric conductors in its 9% schedule, which gives 18% with state tax (Notification 9/2025-Central Tax (Rate) (opens in a new tab)). An inter-state purchase carries 18% IGST (Notification 9/2025-Integrated Tax (Rate) (opens in a new tab)). Ask your CA about input tax credit for your use.

Questions to ask suppliers

  • What is the ISI licence number, and is this conductor, core count, size and armour in its scope?
  • Is this cable to IS 7098 (Part 1) or IS 1554 (Part 1), and what is the full cable code?
  • What drum lengths can you supply, and are part drums or cut lengths possible?
  • Will each drum come with its routine test report (conductor resistance and high voltage test)?
  • If I ask for a fire-performance type, which legend will be on the sheath?
  • Is the rate per metre delivered to my site, with GST shown separately?

Red flags

  • A drum label or sheath marking that does not match the quoted code, size or number of cores.
  • No maker's name along the sheath, or no ISI mark on a cable that must carry it.
  • A conductor that measures smaller, or a resistance well above the value in IS 8130 for the size, when tested.
  • Drum lengths shorter than invoiced.
  • A licence number that does not show up on Manak Online or the BIS Care app, or shows a different maker or product.
  • A request to pay a personal bank account or UPI ID that does not match the supplier's GST-registered name.

How Indibaba can help

Tell Indibaba AI what you need, for example "LT power cable, IS 7098 Part 1, 3.5 core 185 mm² A2XFY, 1,200 metres in 300 metre drums, routine test reports, delivered to Vapi", or use the requirement form. Indibaba AI drafts the requirement and nothing goes to suppliers until you confirm it. It reaches suppliers listed under wires and cables and the RFQ market, where other sellers can quote. Indibaba is new, so some categories still have few suppliers. Suppliers that Indibaba has checked carry the Indibaba Certified badge; others show "Not checked yet".

Rules as of 18 November 2026. This article explains public rules in plain English. For a decision about your business, check the official notification or ask your CA.

Frequently asked questions

What does A2XFY mean on a cable?

It is the cable code from IS 7098 (Part 1): A for aluminium conductor, 2X for XLPE insulation, F for steel strip armour and Y for a PVC outer sheath. A copper cable has no conductor letter, for example 2XFY.

Is the ISI mark compulsory for power cables?

Yes. PVC insulated heavy-duty cables to IS 1554 and XLPE insulated cables to IS 7098 are listed under the Cables (Quality Control) Order, 2020.

What is the GST rate on power cables?

18%. Insulated wire and cable under HSN 8544 is in the 9% central tax schedule of Notification 9/2025-Central Tax (Rate), so a sale within a state carries 9% CGST and 9% SGST.

What should a cable drum label show?

Under IS 7098 (Part 1): the standard, the maker, the type and voltage grade, number of cores, conductor size, cable code, length on the drum, gross mass, country and year of manufacture.

Sources

We checked the facts in this article against these sources on 18 November 2026.